SharpEye 40/40C-M Multispectrum Hydrogen & Hydrocarbon Flame Detector
Spectrex

SharpEye 40/40C-M Multispectrum Hydrogen & Hydrocarbon Flame Detector

Quad-Sense IR3 flame detector for both hydrogen and hydrocarbon fires, with detection at up to 215 ft (65 m) in under five seconds.

ATEXIECExFMCSAEACSIL 3
Contact GDS for current pricing, availability, and lead time. Available configurations may vary by application.
Manufacturer
Spectrex
Category
Flame Detectors
Mounting
Fixed
Gas / hazard
Hydrogen fire, Hydrocarbon fire
Approvals
ATEX, IECEx, FM, CSA, EAC, SIL 3
Typical applications
Refineries, Petrochemical, Offshore, LNG / Natural Gas, Tank Farms / Storage, Manufacturing / Processing

Why customers choose this product

Detects hydrogen and hydrocarbon fuel and gas fires, with a 1 sq ft (0.1 m²) n-heptane pan fire seen at up to 215 ft (65 m).

Four IR sensors separate real flames from background radiation, so false alarms stay rare.

Heated optics and a −40 to 167 °F (−40 to 75 °C) range keep it working in harsh weather.

Built-in IR test continuously checks the optics and electronics. An event log records past alarms.

Universal wiring with relay, 0–20 mA, HART, and RS-485 Modbus outputs. 150,000-hour MTBF, SIL 3 compatible, and a three-year warranty.

Where it's used

Typical facilities and process areas where this product protects people and assets.

Refineries
Petrochemical
Offshore
LNG / Natural Gas
Tank Farms / Storage
Manufacturing / Processing

Technical specifications

Key parameters below. For full datasheets, ratings, and ordering options, contact GDS.

ManufacturerSpectrex
CategoryFlame Detectors
DetectionMultispectrum Quad-Sense triple IR (IR3)
Range (1 sq ft n-heptane)Up to 215 ft (65 m) at highest sensitivity; five sensitivity levels
Hydrogen fire rangeUp to 118 ft (36 m) for a 30 × 10 in. (0.75 × 0.25 m) plume fire; methane and LPG plume fires 150 ft (45 m)
Response timeTypically < 5 seconds
Field of viewHydrogen 90° × 90°; other fuels 80° × 80°
Operating temperature−40 to 167 °F (−40 to 75 °C)
Power24 V DC nominal (18–32 V DC); standby 3 W max (8 W heated), alarm 4.2 W max (9 W heated)
OutputsAlarm, fault, and auxiliary relays (2 A at 30 V DC); stepped 0–20 mA with HART; RS-485 Modbus
EnclosureCopper-free aluminum, polyurethane painted; IP66 / IP68, NEMA 250 6P
Cable entries2 × ¾-in. NPT or 2 × M25
Dimensions / weight4 × 4.6 × 6.18 in. (100.6 × 117 × 155 mm); 2.8 lb (1.3 kg)
Hazardous areaATEX/IECEx Ex db eb IIC T4 Gb, Ex tb IIIC T100 °C Db; FM/FMC/CSA Class I Div 1 Groups B, C, D; TR CU (EAC). INMETRO pending.
PerformanceEN 54-10, FM 3260; SIL 3 compatible (IEC 61508)
Flame simulatorFS-1400 Flame Simulator (listed in the 40/40C-M datasheet)
WarrantyThree years
ApprovalsATEX, IECEx, FM, CSA, EAC, SIL 3

Add this product to a quote request

Tell us the details and we'll come back with pricing, availability, and lead time — usually the same day.

Related products

Others in the Flame Detectors range and from Spectrex.

Request pricing & availability

Send us the details and our team will get you a quote and lead time — usually the same day.

Request a Quote